Installation and operating instructions 34 BATCHCONTROL
Object No
Index
Value (default)
Description
Dimension
Format
min
max
access
Descriptor
transfer
Description
0000 = off
0001 = binary
input
0010 = analogue
input
0011 = binary
output
0100 = pulse
width modulated
output
0101 = customer
program
30y2H Binary input parameter and PDO definition (only valid if 30y1.1 = 01H)
30y2H 00H 4 Number of entries without byte - - r - -
30y2H 01H 0 Function of Input without byte 0 20 r/w - D Bit 3 - 0: Function of Input
0000 = without
function (off)
0001 = Start of
batching
0010 = Stop of
batching
(emergency shut-
down)
0011 = Input for
Bus
0100 = customer
program
Bit 4: Polarity of Input
0 = high active
1 = low active
30y2H 02H 0 Definition for shut-down without byte 0 63 r/w - d
Bit 0: 1 = output 1 switch off if input
is high, 0 = no influencing of the
output
Bit 1: 1 = output 2 switch off if input
is high, 0 = no influencing of the
output
Bit 2: 1 = output 3 switch off if input
is high, 0 = no influencing of the
output
Bit 3: 1 = output 4 switch off if input
is high, 0 = no influencing of the
output
Bit 4: 1 = output 5 switch off if input
is high, 0 = no influencing of the
output
Bit 5: 1 = output 6 switch off if input
is high, 0 = no influencing of the
output
30y2H 03H 0 Status of Input without byte 0 1 r y1H - Bit 0: actual status of Input
0 = Input is off
1 = Input is on
30y2H 04H 4
Sending function for Index
03H
without byte 0 4 r/w - d
Bit 3-0: Sending function change of
status
Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: activation of function
1 = no message
output
0 = activation of
message output
30y3H Analogue input and PDO definition (only valid if 30y1.1 = 02H)
30y3H 00H 10 Number of entries without byte - - r - -
30y3H 01H 0 Function of Input without byte 0 20 r/w - d Bit 3 - 0: Function of Input
0000 = without
function (off)
0001 = input for
bus