Manual

Installation and operating instructions 32 BATCHCONTROL
Object No
Index
Value (default)
Description
Dimension
Format
min
max
access
Descriptor
transfer
Description
volume is to high, 0 = no
influencing of the output
Bit 1: 1 = output 2 switch off if
volume is to high, 0 = no
influencing of the output
Bit 2: 1 = output 3 switch off if
volume is to high, 0 = no
influencing of the output
Bit 3: 1 = output 4 switch off if
volume is to high, 0 = no
influencing of the output
Bit 4: 1 = output 5 switch off if
volume is to high, 0 = no
influencing of the output
Bit 5: 1 = output 6 switch off if
volume is to high, 0 = no
influencing of the output
3003H 07H - Actual status without byte 0 1 r 05H -
Bit 0: 1 = Limit value exceeded, 0 =
okay
3003H 08H 4
Sending function for Index
07H
without byte 0 4 r/w - d Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: activation of function
1 = no message
output
0 = activation of
message output
301xH Electronic temperature sensor
3011H Sensor parameter
3011H 00H 2 Number of entries without byte - - r - -
3011H 01H 1.0 Factor for scaling without float 0,001
1000,
0
r/w - d
3011H 02H 0.0 Offset for scaling °C float -100,0 100,0 r/w - d
3012H Measurement values and PDO definition
3012H 00H 3 Number of entries without byte - - r - -
3012H 01H 0,0 Measuring value °C float -10 +100 r 11H - actual measured temperature
3012H 02H 4
Sending function for index
01H
without byte 0 4 r/w - d
Sending function of temperature
output (repeat time depends on
index 3)
Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: activation of function
1 = no message
output
0 = activation of
message output
3012H 03H 250 Repeat time ms word 50 5000 r/w - d Repeat time for the value
3013H Alarm values and PDO definition
3013H 00H 4 Number of entries without byte - - r - -
3013H 01H 20 Lower limit value °C float -10 +80 r/w - d
Warning message when value
remains below limit
3013H 02H 70 Upper limit value °C float 0 +100 r/w - d
Warning message when value
exceeds limit
3013H 03H 0 Status of measuring input without byte 0 15 r 12H -
Bit 0: 1 = lower limit value is
exceeded
Bit 1: 1 = upper limit value is
exceeded
Bit 2: 1 = sensor cable break
Bit 3: 1 = sensor short circuit
3013H 04H 4
Sending function for index
03H
without byte 0 4 r/w - d Sending function change of status