Manual

Installation and operating instructions
BATCHCONTROL
Object No
Index
Value (default)
Description
Dimension
Format
min
max
access
Descriptor
transfer
Description
1 = no message
output
0 = activation of
message output
3002H 03H 0,0
Volume flow with time
constant
l/s float -15,1 15,1 r 02H -
actual measurement flow value with
time constant
3002H 04H 4
Sending function for Index
03H
without byte 0 4 r/w - d
Sending function Measurement
value with time constant
Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: activation of function
1 = no message
output
0 = activation of
message output
3002H 05H 0,0 Currently measured volume l float -1000 1000 r 03H d Currently totalized volume
3002H 06H 4
Sending function for Index
05H
without byte 0 4 r/w - d
Bit 2-0: Sending function volume
counter
Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: activation of function
1 = no message
output
0 = activation of
message output
3003H Alarm values and PDO definition
3003H 00H 8 Number of entries without byte - - r - -
3003H 01H 1 Maximum volume flow l/s float 0,0001 15,1 r/w - d
Limit value for volume flow (without
time constant) with emergency
shut-down
3003H 02H 0 Definition for shut-down without byte 0 63 r/w - d
Bit 0: 1 = output 1 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 1: 1 = output 2 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 2: 1 = output 3 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 3: 1 = output 4 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 4: 1 = output 5 switch off if
volume flow is to high, 0 = no
influencing of the output
Bit 5: 1 = output 6 switch off if
volume flow is to high, 0 = no
influencing of the output
3003H 03H - Actual status without byte 0 1 r 04H -
Bit 0: 1 = Limit value exceeded, 0 =
okay
3003H 04H 4
Sending function for Index
03H
without byte 0 4 r/w - d Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: activation of function
1 = no message
output
0 = activation of
message output
3003H 05H 1,0 Maximum volume l float 0,0001 100,0 r/w - d
Limit value for counted volume with
emergency shut-down
3003H 06H 0 Definition for shut-down without byte 0 63 r/w - d Bit 0: 1 = output 1 switch off if