Installation and operating instructions 30 BATCHCONTROL
E 2 CAN parameter
Object No
Index
Value (default)
Description
Dimension
Format
min
max
access
Descriptor
transfer
Description
10xxH CANopen parameter
1000H 00H Device type without long 0 r - - 0x00000014 (const. value)
1008H 00H Manufacturer Device Name without string - - r - - “IFC “
1009H 00H
Manufacturer Hardware
Version
without string - - r - - “014 “
1010H Parameter save
1010H 00H 1 Number of entries without byte - - r - -
1010H 01H
Save all parameters in
EEPROM
without long - - r/w - d
Save databytes: 65H 76H 61H 73H
Read: 00H 00H 00H 01H
1011H Parameter recall
1011H 00H 1 Number of entries without byte - - r - -
1011H 01H 1
Recall all parameters from
EEPROM to RAM
without long - - r/w - d
Recall databytes: 64H 61H 6FH
6CH
Read: 00H 00H 00H 01H
1017H 00H 250 Consumer heartbeat time ms word 0 65535 r/w - d
1018H Identity Object
1018H 00H 4 Number of entries without byte - - r - -
1018H 01H Vendor Id without long - - r - -
1018H 02H Product code without long - - r - -
1018H 03H Revisionsnumber without long - - r - -
1018H 04H Serialnumber without long - - r - -
300xH Flow sensor parameter
3001H Sensor parameter
3001H 00H 7 Number of entries without byte - - r - -
3001H 01H 1 Full scale range l/s float 0,0015 15,1 r/w - d
Full scale value, basis for values
given as percentage values
3001H 02H 1 Time constant S float 0,1 99 r/w - as
Time constant for output value, of
no significance for
BATCHCONTROL
3001H 03H 15 Meter size mm float 2,5 40 r/w - as Meter size of tube
3001H 04H 3,3 Sensor constant without float 0,5 9,9 r/w - as Calibration constant of Sensor
3001H 05H 0 Zero point l/s float -1,0 +1,0 r/w - as Zero point of Sensor
3001H 06H 0 Flow direction without byte 0 1 r/w - as
0 = as printed on
instrument
1 = contrary to
imprint
3001H 07H 0 Auto zero function - byte 0 1 r/w - d Zero point calculation
Bit 0: Activation of function
1 = function
active
0 = function
switched off
3002H Measurement values and PDO definition
3002H 00H 6 Number of entries without byte - - r - -
3002H 01H 0,0
Volume flow without time
constant
l/s float -15,1 15,1 r 01H -
Actual measurement flow value
without time constant
3002H 02H 4
Sending function for Index
01H
without byte 0 4 r/w - d
Sending function measurement
value without time constant
Bit 1-0: Priority
00 = PDO 0
01 = PDO 1
10 = PDO 2
11 = PDO 3
Bit 2: Activation of function
E