ALTOSONIC V
ModBus Manual 0300 rev07 E 7.30855.35.00 Page 56 of 64
See for the communication runtime errors also the ALTOSONIC V Modbus Manual.
Err no. In function Problem Consequence
W: 33 Modbus master Poll block not send due to transmit error
W: 34 Modbus master Poll block response time-out occurred
W: 35 Modbus master Invalid Slave ID in response
W: 36 Modbus master Invalid function in response
W: 37 Modbus master Response not correct
W: 38 Modbus master Error handling function 1,2
W: 39 Modbus master Error handling function 3,4
W: 40 Modbus master Error handling function 5
W: 41 Modbus master Error handling function 6
W: 42 Modbus master Error handling function 15
W: 43 Modbus master Error handling function 16
W: 44 Modbus master Exception received
W: 45 Modbus master Error unpacking Boolean data
W: 46 Modbus master Error unpacking integer data
W: 47 Modbus master Error unpacking long integer data
W: 48 Modbus master Error unpacking float data
W: 49 Modbus master Error unpacking double data
W: 50 Modbus master/slave Error incorrect message length
W: 51 Modbus master/slave Invalid CRC or LRC received
W: 52 Modbus master/slave Error receive buffer saturated
W: 53 Modbus master/slave UART error ( parity, framing, overrun )
W: 54 Modbus master/slave Transmit buffer not empty for new
transmission
W: 55 Modbus slave Unsupported function requested
W: 56 Modbus slave Unsupported register(s) requested
W: 57 Modbus slave Requested data Level and function
mismatch
W: 58 Modbus slave Too many data point (registers) requested
W: 59 Modbus slave Error unpacking received data
W: 60 Modbus slave Broadcast not allowed