Manual
ALTOSONIC V
ModBus Manual 0300 rev07 E 7.30855.35.00 Page 45 of 64
246 491 F32+R Batch stop: Average Density external 4 8 kg/m3
247 493 F32+R Batch stop: Average Flow external 4 8 m3/h
248 495 F32+R Batch stop: Average Inst. K-Factor external 4 8 [ ]
249 497 F32+R Batch stop: Average New K-Factor external 4 8 [ ]
250 499 F32+R Batch stop: Average Diff. K-Factor Inst.. New 4 8 %
8.6 Field 5 (Read only Double Field)
This data is read only and can be accessed with Modbus function 3 and 4 in Modbus slave mode and
with functions 6 and 16 in Modbus master mode. A double is a float 64 bit type
By default the start addresses are mapped to address 6000 (default value)
start address
NotModiconComp
start address
ModiconComp
Type+Access
Description
Level
Level
Level
Remark
1 1 F64+R Resetable totaliser: proces sum 1 Liter
2 5 F64+R Flow process 1 m3/h
3 9 F64+R Sound velocity average 1 m/s
4 13 F64+R Resetable totaliser: standard sum 2 liter
5 17 F64+R Flow standard 2 m3/h
6 21 F64+R Resetable totaliser: mass sum 2 kg
7 25 F64+R Flow mass 2 ton/hr
8 29 F64+R Reserved
9 33 F64+R Resetable totaliser: proces forward 1 liter
10 37 F64+R Resetable totaliser: proces reverse 1 liter
11 41 F64+R Resetable totaliser: standard forward 2 liter
12 45 F64+R Resetable totaliser: standard reverse 2 liter
13 49 F64+R Resetable totaliser: mass forward 2 kg
14 53 F64+R Resetable totaliser: mass reverse 2 kg
15 57 F64+R Resetable totaliser: external flow meter proces 8 liter
16 61 F64+R Resetable totaliser: external flow meter standard 8 liter
17 65 F64+R Resetable totaliser: external flow meter mass 8 kg
18 69 F64+R Non resetable totaliser: proces sum 1 m3
19 73 F64+R Non resetable totaliser: proces forward 1 m3
20 77 F64+R Non resetable totaliser: proces reverse 1 m3
21 81 F64+R Non resetable totaliser: standard sum 2 m3
22 85 F64+R Non resetable totaliser: standard forward 2 m3
23 89 F64+R Non resetable totaliser: standard reverse 2 m3
24 93 F64+R Non resetable totaliser: mass sum 2 ton
25 97 F64+R Non resetable totaliser: mass forward 2 ton
26 101 F64+R Non resetable totaliser: mass reverse 2 ton