Owner's manual
4
With each in/output module a certain in/output function can be realised, see following overview:
In/Output
module
Function Electrical data
P-SA passive current output Current: 4..20 mA
Working voltage: 8.. 30 V DC
Voltage drop: 8 V at 4 mA
FA-ST passive pulse/status output or
control input (selectable through
software options)
Working voltage: 6..30 V DC
Working current: < 110 mA
Voltage drop
in ON-state: < 2 V at 110 mA
Leakage current
in OFF-state: < 900 µA at 30 V
Control input
Input voltage LOW level: < 3 V
Input voltage HIGH level: > 7 V
Frequency range: 0.. 12 KHz
DC-I intrinsically safe voltage source,
to be used in combination with
modules P-SA and FA-ST
Voltage: 20 V DC
Maximum current: 30 mA
Internal resistance: 260 Ω
F-PA passive Fieldbus interface conform FISCO model
The functionality of the terminals for signal in/outputs is depending on the version of the
IFC090 i-EEx electronic-unit installed. Each version is equipped with a different pair of in/output
modules. Following versions are possible:
IFC090 i-EEx version Order no. MODIS module Terminal desi
g
nation
Ex-i1 2.11582.01 P-SA FA-ST
I⊥
IB1
B1⊥
Ex-i2 2.11582.03 P-SA F-PA
I⊥
ID
D⊥
Ex-i3 2.11582.02 P-SA DC-I I+ I
Ex-i4 2.11582.04 FA-ST F-PA B1
B1⊥
D
D⊥
Ex-i5 2.11582.05 FA-ST DC-I B1+ B1
Ex-i6 2.11582.06 FA-ST FA-ST B2
B2⊥
B1
B1⊥
The non-intrinsically safe terminals for the power supply 1L and 0L have to be wired conform
the relevant standard code of practice for electrical apparatus for use in potentially explosive
Connection power supply
(non-intrinsically safe)
Connection of signal-in/outputs
(intrinsically safe)