Datasheet

Rated operational power
Utilization category Voltage (V) No. of phases No. of poles Power (kW)
AC-4 220 - 240 1 2 0,75
AC-4 380 - 440 1 2 1,50
AC-23A 220 - 240 3 3 3,70
AC-23A 380 - 440 3 3 7,50
AC-23A 500 - 500 3 3 7,50
AC-23A 660 - 690 3 3 7,50
AC-23A 110 - 120 1 2 0,75
AC-23A 220 - 240 1 2 2,50
AC-23A 380 - 440 1 2 3,70
AC-23A 500 - 500 1 2 4
AC-23A 660 - 690 1 2 4
Max. Fuse rating IEC
Fuse characteristic No. of Fuses Current (A)
gG 1 25
UL60947-4-1 , UL508
Rated insulation voltage Ui
Voltage (V) AC / DC
600 AC
Rated thermal current
Current (A) Ambient temperature (°C) Additional Text
20 0 - 40 --
CSA
Rated insulation voltage Ui
Voltage (V) AC / DC
600 AC
Rated thermal current
Current (A) Ambient temperature (°C) Additional Text
20 0 - 40 --
GENERAL TECHNICAL INFORMATION
Tightening torque of screws
tightening torque (Nm) tightening torque (lb-in)
1 9
Rated short-time withstand current Icw
Time (s) Current (A)
1 200
Size of conductor
composition of conductor Min. / Max. value No. of conductor per terminal
Cross section (mm²) or
(AWG/kcmil)
Material of the wire
solid wire Min. 1 0.75mm² Copper
solid wire Min. 2 0.75mm² Copper
flexible wire Min. 1 0.75mm² Copper
flexible wire Min. 2 0.75mm² Copper
flexible wire Max. 2 AWG 12 Copper
flexible wire Max. 2 2.5mm² Copper
Single-core or stranded wire Max. 2 AWG 10 Copper
Single-core or stranded wire Max. 2 4mm² Copper
flexible wire with ferrule according to DIN 46228 Min. 1 0.75mm² Copper
flexible wire with ferrule according to DIN 46228 Min. 2 0.75mm² Copper
flexible wire with ferrule according to DIN 46228 Max. 2 2.5mm² Copper
Approbations
Specification Marking
EAC
CE marking
UK Directives
Lloyd´s Register EMEA
Datasheet CH10
06.15.2023 04:31 AM v3.5 https://www.krausnaimer.com Page 2 of
3