User manual
33
• installationoftheelectricalinstallationmaterial.
• typeofsupplynetwork(TNSystem,IT-system,TT-system)
and the resulting connection conditions (grounding
without a special grounding conductor, protective
grounding,necessaryadditionalmeasures,etc…).
Follow the connection diagrams that are included for con-
nection.
Damagedor partially damaged devicesmay not be con-
nected or used.
Before installation, ensure that the wires to be connected
to the device are not live.
Observethe rules of electrical engineering and DINVDE
0100
General notes
The PRCD-S is a portable dierential residual current
device with electronic residual current evaluation that
switches on all poles and was designed for connection
within a cable.
PRCD-S stands for: Portable Residual Current Device,
S=Safety
Theportablesafetyswitch PRCD-Swasdevelopedbased
on the recommendation of the BG for connection to un-
known outlets and makes safe current consumption from
thesesupplypointspossible.
ThePRCD-SinspectthesocketifthephaseL,theneutral
conductor N and the protective conductor PE is
•present,
•properlyconnected,
•arenotinverted
Andswitchononlyonasafesocketoutlet
The ground wire is checked when switched on and mon-
itored during operation.
ThePRCD-Srecognizessystem errorsin the xedinstall-