User Manual
ATX Shutdown Relay
Connect the female ATX lead to the motherboard’s 
power switch connection (usually marked “PWR”, 
“PWRSW”, “PWSW”, or “PWBT”). This is the 
connection that would normally receive the chassis 
power button directly.
To Motherboard
Chassis Power 
Button
From 
Koolance 
Unit
There is no polarity orientation with the ATX 
lead. For computer use, connect the male 
shutdown lead from the Koolance unit to your 
computer’s front chassis power button.
The ATX lead is responsible for sending the shutdown signal if any sensor 
reaches the preset temperature (detailed later). This can be configured as 
NC (normally closed) or NO (normally open) by attaching the two-pin wire 
to the corresponding pins. For computers, use “NO” (normally open).
To Motherboard
The rear of the unit accepts various connections to integrate with your cooling system. The 
temperature sensors may come pre-connected. If not, connect them per the diagram below:
Power Connection 
Plug the included power harness into 
the location on the rear of the unit 
marked “Power”. To this, connect a 12 
Volt 4-pin Molex plug from your power 
supply.
Fan Connection 
This unit has three connections to power radiator fans. Multiple fans can be combined into 
a single plug. (A fan wiring harness is optionally available from Koolance).
CAUTION: The total combined amperage of all fans connected to the unit can 
not exceed 4.5A. The maximum load on a single fan header is 2.0A.
!
Flow Meter Connection
The cooling system can show values for one Koolance flow meter (sold separately). Connect 
a flow meter to the appropriately labeled plug. (Note: INS-FM18 and INS-FM19 should 
connect to the plug labeled “INS-FM17”.)
CTR-CD1224 User Manual v 1.0
1
2
Pump Connection and Voltage Jumper
Plug the included pump wiring harness into the rear 
“Pump” connector. Different plugs are provided to 
connect a single 12 Volt or 24 Volt DC pump. (Max. 
output power = 36W @12V, 50W @24V.) Do not 
connect more than one pump.
CAUTION: Do not power 12V pumps at the 24V setting! This 
can permanently damage the pump.
!
TEMP: Temperature sensors 
shown on the front display
POWER: Connection from 
power supply, 12VDC
FAN: Radiator fan connections 
(2.0A max per plug, 4.5A total)
ATX: Lead for 
power shut-
down feature
PUMP: 
External 
pump
INS-FM17/INS-FM16: 
Connect an optional flow 
meter to display flow rate
ON/SYNC/OFF: 
Adjusts LED lighting 
of INS-FM16 flow 
meter
Pump Voltage Jumper: Configure the pump 
output for a maximum of 12-Volts or 24-Volts. 
Misconfiguration could damage the pump!
Shutdown Relay: Configure the safety 
shutdown relay (labeled “ATX”) as Normally-
Open (NO) or Normally-Closed (NC).
The pump voltage jumper 
should be set for the maximum 
voltage capability of the pump, 
either 12V or 24V.