GASKET Cleaning Guide
Product error guide
Type Cause Display Lamp Solution Release Status
No water
supply
No water supply
in time for ice
production
POWER lamp
blinks
1.Check the amount
of w at e r s u pp l y
2.Check the connections
Automatically reverts
to initial mode after 1 hour
after turning off, or resets
the error when the machine
is switched to stop mode
Stop
Ice
making
delayed
No completed ice
making within 65min.
(10sec detection of
Float_L )
POWER lamp
blinks
1. Clean the condenser
2. Clean the evaporator
3. Use machine below
100F ambient
temperature.
4. Check the condenser
section (Contact service
center)
Error resets when the
machine is switched to stop
mode
Stop
Harvest
delayed
Not dispensing ice
cubes within 5min
(Non-sensing ICE
FULL) : happens 3
times in a row
POWER lamp
blinks
1. Clean the evaporator
(remove incomplete ice
cubes)
2.
Use the machine
above 50F
ambient temperature.
3. Check the condenser
section
(Contact service center)
Error resets when the
machine is switched to stop
mode
Stop
Detected
a full
load of
ice
Storage is full of ice FULL lamp
is on
Remove some ice
When no detection of
ICE FULL after a double
check(Low), automatically
converts to ice making mode
Stop
High
pressure
error
Detecting high
pressure swith
disorder(High)
for 10sec.
POWER lamp
blinks
and ERROR lamp
is on
1. Clean the condenser
2. Check the fan motor
working(Contact
service center)
Resets once normal
condition of high pressure
switch is detected for
10sec.(Low),returns to initial
mode.
Stop
High
pressure
error
Detecting high
pressure switch
disorder(High)
3 times in a row
POWER lamp and
ERROR lamp
blinks
Returns to initial mode 1
hour after turning off, or
resets the error when the
machine is switched to stop
mode
Stop
Water
supply
error
Detecting upper
sensor(High) over
10seconds before
detecting lower
senso
r(Low)
FULL lamp
blinks
Check the water valve
Resets when cause of the
error is solved or when the
machine is switched to stop
mode.
Stop