Owner's Manual
KT-LFPES512100
https://www.kon-tec.eu/
4/5
Kon-TEC sp. z o.o.
Boya-Żeleńskiego 12, 35-105 Rzeszów
T: +48 572 001 151 E: info@kon-tec.eu W: www.kon-tec.eu
2.2.4.2 Inverter tab
VE Congure Inverter
Parameter
Setting
DC input low shut-down 46V
DC input ow restart 51.2V
DC input low pre-alarm 51.2V
2.2.4.3 ESS assistant setting (if you are using your battery in a grid connected system)
2.2.4.2 Charge tab
VE Congure Charge Parameter Setting
Battery type 48V
Charge curve Fixed
Absorption voltage 56.0 V
Float·voltage 54.6 V
Absorption time 1 hr
2.2.3.5 Congure MPPT via Victron connect.
MPPT Parameter Setting
Battery voltage 48V
Absorption voltage 56.0V
3.1.4.1 General tab
• Check the „Enable battery monitor” function
• Set the battery capacity to the total capacity of the battery, each model is 100Ah
• The other parameters („State of charge when bulk nished”and “Charge efciency”) can be left to their default setting.
3.1.4 VE CONFIGURE SETTINGS