Installation Guide
8 TT-1596 3/15
12. Mount two circuit breakers onto the bracket.
For the 14RESA, 70 amp circuit breakers:
a. Use 4 X-67-132 thread-forming screws and 4
X-400-145 spacers for each circuit breaker.
Install the spacers between the circuit breaker
mounting tabs and the bracket. See Figure 10.
b. Connect the circuit breakers to the APM
contactors using 4 leads LN-0607-0606
provided with the circuit breaker kit. See
Figure 9 and the wiring diagram in Section 8 for
circuit breaker connections.
1
tt1596
1. Mounting bracket GM85151
2. Spacer X-400-145, qty. 8. Locate spacer between circuit
breaker mounting tab and bracket as s hown.
3. Screw X-67-132, qty. 8
4. Circuit breaker, 70 Amp, GM28743, qty. 2
32 4
Figure 10 70 Amp Circuit Breaker Mounting, 14RESA
For the 20RESA or 20RESB, 100 amp circuit breakers:
c. Use 2 X-67-132 thread-forming screws to
attach each circuit breaker to the mounting
bracket. See Figure 11.
d. Connect the circuit breakers to the APM
contactors using 4 leads LN-0407-0606
provided with the circuit breaker kit. See
Figure 9 and the wiring diagram in Section 8 for
circuit breaker connections.
1
tt1596
1. Circuit breaker, 100 amp, GM77390, qty. 2
2. Screw X-67-132, qty. 4 (bottom screws are not shown)
3. Mounting bracket GM85151
2
3
2
Figure 11 100 Amp Circuit Breaker Mounting,
20RESA and 20RESB