Product Card

KH275
Engine type
P126TI
Alternator type KH01380T
Performance class
G3
GENERAL CHARACTERISTICS
Frequency (Hz)
Voltage (V)
Standard control panel
POWER
ESP PRP
Voltage
kWe kVA kWe kVA
Standby Amps
DIMENSIONS COMPACT VERSION
Length (mm) 2900
Width (mm) 1300
Height (mm) 1670
Dry weight (kg) 2310
Tank capacity (L) 390
DIMENSIONS SOUNDPROOFED VERSION
Commercial reference of the enclosure M227
Length (mm) 4004
Width (mm) 1380
Height (mm) 2145
Dry weight (kg) 3160
Tank capacity (L) 390
Acoustic pressure level @1m in dB(A) 83
Sound power level guaranteed (Lwa) 102
This document is not contractual - Kohler Co. reserves
the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-05001 (KH275) 03/17
DESCRIPTIVE
Kohler Co. Provides one-source responsibility for the
generating system and accessories
The generator set and its components are prototype-
tested, factory-built, and production-tested
A one-year limited warranty covers all systems and
components
Electronic governor
Mechanically welded chassis with antivibration
suspension
Main line circuit breaker
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual
operating hours in variable load applications, in accordance with ISO
8528-1. ESP : The standby power rating is applicable for supplying
emergency power in variable load applications in accordance with ISO
8528-1. Overload is not allowed
TERMS OF USE
According to the standard, the nominal power assigned by the genset is
given for 25°C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions
in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generator sets used indoor, where the acoustic pressure levels
depend on the installation conditions, it is not possible to specify the
ambient noise level in the operating and maintenance instructions.
You will also find in our operating and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriate preventive measures.
Charger DC starting battery with electrolyte
24 V charge alternator and starter
Optional control panel
Optional control panel
415/240 213 266 194 242 370
400/230 220 275 200 250 397
380/220 220 275 200 250 418
200/115 220 275 200 250 794
240 TRI 213 266 194 242 640
230 TRI 220 275 200 250 690
Acoustic pressure level @7m in dB(A) 73
Optional control panel
50
400/230
APM303
DEC4000
APM802
M80
Radiator for core temperature of 48/50°C max with
mechanical fan
Protective grille for fan and rotating parts (CE option)
9 dB(A) silencer supplied separately
Delivered with oil and coolant -30°C
Manual for use and installation
220 TRI 220 275 200 250 722

Summary of content (5 pages)