TP-6946 3/1666 Section 7 Changing the Service Disconnect Position
6. Use cable ties to secure the leads out of the way.
7. Reconnect power to the control circuit. Follow the
instructions in Section 6.5.
8. Use Kohlerr SiteTecht software to change the
service disconnect position setting to Emergency.
See the procedure in Section 7.2.1.
1. Engine start bypass circuit leads 4B and 4D connected to
TB1 on the controller’s main circuit board.
1
GM95679
Figure 7-5 Engine Start Bypass Circuit Connection
7.2.3 Connection Changes for Service
Disconnected Lamp Operation
If a transfer switch with the new transformer assembly is
converted to use the Service Disconnect to Emergency
position, change the connections described in this
section for correct operation of the Service
Disconnected lamp. Follow the instructions in the
procedure for MCCB or ICCB models as applicable to
your unit.
Procedure for MCCB Models
1. At the TR relay on the transformer panel,
disconnect lead DL2 from terminal 3 and connect it
to terminal 6. See Figure 7-6.
2. Find the quick-connect QCON1 in lead USD,
located between connectors P3 and P4. See
Figure 7-7. Disconnect leads USD and USD1 at
the quick--connect and tape the ends.
1
GM95677
1. Disconnect lead DL2 from terminal 3 and connect to
terminal 6.
Figure 7-6 Lead DL2 Reconnection on the
Transformer Panel, MCCB Models