Product Manual

TP-6946 3/1664 Section 7 Changing the Service Disconnect Position
7.2.1 Procedure to Change the Service
Disconnect Position Setting on
the Controller
1. Use a USB cable to connect your laptop PC to the
MPAC controller. See Figure 7-3.
2. Start SiteTecht and wait for it to connect to the
MPAC controller.
3. Click on Set Mpac Password and enter the
distributor password. Obtain the password from
the Kohler Power Systems Generator Service
Department.
4. Find the Service Disconnect Position setting in the
ATS Connection Configuration group. See
Figure 7-4.
5. Change the Service Disconnect Position setting to
Source E.
6. Apply changes to save the new setting.
1
GM85888
1. USB connection (below port cover)
Figure 7-3 USB Connection for SiteTech
2
1. Click Set Mpac Password and enter the distributor-level password
2. Service Disconnect Position Setting
3. Apply changes
3
1
Figure 7-4 Service Disconnect Position Setting in SiteTech