Product Manual

TP-6946 3/1624 Section 2 Installation
2.9.2 Engine Start Connection
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
WARNING
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
Prevent the generator set from starting by pressing the
OFF button on the generator controller; disconnecting
power to the generator engine start battery charger, if
installed; and disconnecting all generator engine start
battery cables, negative (--) leads first.
Connect the generator set remote starting circuit to the
engine start connections located on terminal block TB1
on the transformer assembly, which is typically mounted
on the right wall inside the enclosure. The engine start
terminals are labeled with a red decal. See Figure 2-3
for the transformer assembly with the engine start
terminal block. See Figure 2-13 and Figure 2-14 for
typical locations of the engine start contacts inside the
enclosure.
Refer to the generator set installation manual for wire
size specifications.
Engine Start Contacts
Contact Rating 2 A @ 30 VDC/250 VAC
1. Engine start contacts 3 and 4 (TB1 on transformer
assembly)
2. Control circuit isolation switch (see Section 6.5)
ADV-7708
1
Right Side View
2
Figure 2-13 Engine Start Contact Terminal Block
Location, MCCB Models (typical)
1
1. Engine start contacts 3 and 4 (TB1 on transformer
assembly)
2. Control circuit isolation switch (see Section 6.5)
ADV-7784
Right Side View
2
Figure 2-14 Engine Start Contact Terminal Block
Location, ICCB Models (typical)