Product Manual

TP-6946 3/16 23Section 2 Installation
Drill the entry holes. Cover the transfer switch to
protect it from metal chips and construction grit. Then
drill entry holes for the conductors at the locations
shown on the enclosure drawings. Remove debris from
the enclosure with a vacuum cleaner.
Note: Do not use compressed air to clean the switch.
Cleaning with compressed air can cause debris
to lodge in the components and damage the
switch.
Install and test the power cables. Leave sufficient
slack in the power leads to reach all of the power
connecting lugs on the power switching device. Test the
power conductors before connecting them to the
transfer switch. Installing power cables in conduit, cable
troughs and ceiling-suspended hangers often r equires
considerable force. Pulling cables can damage
insulation and stretch o r break the conductor’s strands.
Test the cables after pulling them into position and
before they are connected to verify that they are not
defective and that they were not damaged during
installation.
Connect the cables. Be careful when stripping
insulation from the cables; avoid nicking or ringing the
conductor. Clean cables with a wire brush to remove
surface oxides before connecting them to the terminals.
Apply joint compound to the connections of any
aluminum conductors.
Refer to the wiring diagram provided with the switch.
The connection points on the contactor are labeled
Normal, Emergency, and Load. Be sure to follow the
phase markings (A, B, C, and N). For single-phase
systems, connect to A and C.
Note: Connect the source and load phases as
indicated by the markings and drawings to
prevent short circuits and to prevent phase-
sensitive load devices from malfunctioning or
operating in reverse.
Tighten the lugs. Verify that all connections are
consistent with drawings before tightening the lugs.
Tighten all cable lug connections to the torque values
shown on the label on the switch. See Figure 2-12.
Carefully wipe off any excess joint compound after
tightening the terminal lugs.
297556
Figure 2-12 Torque Label