Product Manual
TP-6946 3/1614 Section 2 Installation
2.2.3 Storage
Store the transfer switch in its protective packing until
final installation. Protect the transfer switch at a ll times
from moisture, construction grit, and metal chips. Avoid
storage in low-temperature and high-humidity areas
where moisture could condense on the unit. See
Figure 2-2 for acceptable storage temperatures.
Environmental Specifications
Operating Temperature -- 1 5 Cto50C(5F to 122F)
Storage Temperature -- 2 0 Cto70C(--4F to 158F)
Humidity 5% to 95% noncondensing
Figure 2-2 Environmental Specifications
2.2.4 Unp acking
Allow the equipment to warm to room temperature for at
least 24 hours before unpacking to prevent
condensation on the electrical apparatus. Use care
when unpacking to avoid damaging transfer switch
components. Remove dirt and packing material that
may have accumulated in the transfer switch or any of its
components.
Note: Do not use compressed air to clean the switch.
Cleaning with compressed air can cause debris
to lodge in the components and damage the
switch.