Product Manual

TP-6946 3/16 13Section 2 Installation
Section 2 Installation
2.1 Introduction
Kohlerr transfer switches are shipped factory-wired,
factory-tested, and ready for installation. Have the
equipment installed only by trained and qualified
personnel, and verify that the installation complies with
applicable codes and standards. Switch installation
includes the following steps:
D Unpack and inspect the transfer switch upon receipt.
D Verify that the transfer switch voltage and frequency
ratings match the voltages and frequencies of the
sources.
D Install the transfer switch.
D Check the manual operation.
D Connect the controller harness and ground lead.
D Connect the generator set engine start leads.
D Connect the normal power source (utility),
emergency power source (generator set), and load
circuits.
D Connect accessories, if provided.
D Check voltages and operation.
Protect the switch against damage before and during
installation.
The functional tests in Section 5 a re a necessary part of
the installation. Be sure to perform the functional tests,
which include voltage checks and operation tests,
before putting the transfer switch into service.
2.2 Receip t of Unit
2.2.1 Inspection
At the time of delivery, inspect the packaging and the
transfer switch for signs of shipping damage. Unpack
the transfer switch as soon as possible and inspect the
exterior and interior for shipping damage. If damage
and/or rough handling is evident, immediately file a
damage claim with the transportation company.
2.2.2 Lifting
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Use adequate lifting capacity.
Never leave the transfer switch
standing upright unless it is securely
bolted in place or stabilized.
WARNING
Refer to Figure 2-1 for the approximate weight of the
transfer switch in a Type 1 enclosure. For other
enclosures, refer to the specification sheet or the
dimension drawing.
Use a spreader bar to lift the transfer switch. Attach the
bar only to the enclosure’s mounting holes or lifting
brackets; do not lift the unit any other way. Close and
latch the enclosure door before moving the unit.
Amps
MCCB Models, Weight, kg (lb.)
2P 3P 4P
100-150 68 (150) 68 (150) 68 (150)
200 68 (150) 68 (150) N/A
250 81 (178) 81 (178) 81 (178)
400 195 (430) 195 (430) 195 (430)
600-800 200 (441) 200 (441) 200 (441)
1000-1200 N/A 270 (595) 270 (595)
ICCB Models, Weight, kg (lb.)
800 N/A 544 (1200) 635 (1400)
1000-1200 N/A 553 ( 1220) 644 (1420)
1600 N/A 598 (1320) 625 (1380)
2000 N/A 607(1340) 644 (1420)
2500 N/A 625 (1380) 662 (1460)
3000 N/A 644 (1420) 680 (1500)
4000 N/A 907 (2000) 1270 (2800)
Figure 2-1 Approximate Weights with Type 1