Product Card

KD88
Engine type
4045TF220
Alternator type KH00973T
Performance class
G3
GENERAL CHARACTERISTICS
Frequency (Hz)
Voltage (V)
Standard control panel
Optional control panel
Optional control panel
POWER
ESP
PRP
Voltage
kWe
kVA
Standby Amps
200/115 70 88 64 80 254
240 TRI 70 88 64 80 212
230 TRI 70 88 64 80 221
220 TRI 70 88 64 80 231
DIMENSIONS COMPACT VERSION
Length (mm)
1870
Width (mm)
994
Height (mm)
1360
Dry weight (kg)
1088
Tank capacity (L)
180
DIMENSIONS SOUNDPROOFED VERSION
Commercial reference of the enclosure
M128
2300
1060
1680
1508
180
76
Length (mm)
Width (mm)
Height (mm)
Dry weight (kg)
Tank capacity (L)
Acoustic pressure level @1m in dB(A)
Sound power level guaranteed (Lwa)
Acoustic pressure level @7m in dB(A)
94
This document is not contractual - Kohler Co. reserves the right to modify any of the characteristics without notice, in a constant effort to improve the quality of its products.
GBD5-03006 (KD88) 03/17
50
400/230
APM303
DEC4000
M80
DESCRIPTIVE
Kohler Co. Provides one-source responsibility for the
generating system and accessories
The generator set and its components are prototype-
tested, factory-built, and production-tested
A one-year limited warranty covers all systems and
components
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual
operating hours in variable load applications, in
accordance with ISO
8528-1. ESP : The standby power rating is applicable for supplying
emergency power in variable load applications in accordance with ISO
8528-1. Overload is not allowed
TERMS OF USE
According to the standard, the nominal power assigned by the genset is
given for 25°C Air Intlet Temperature, of a barometric pressure of 100
kPA (100 m A.S.L), and 30 % relative humidity. For particular conditions
in your installation, refer to the derating table.
ASSOCIATED UNCERTAINTY
For the generator sets used indoor, where the acoustic pressure levels
depend on the installation conditions, it is not possible to specify the
ambient noise level in the operating and maintenance instructions.
You will also find in our operating and maintenance instructions a
warning concerning the air noise dangers and the need to implement
appropriate preventive measures.
Mechanic governor
Mechanically welded chassis with
antivibration
suspension
Main
line circuit breaker
Radiator for core temperature of 48/50°C max with
mechanical fan
Protective grille for fan and rotating parts (CE option)
9
dB(A) silencer supplied separately
Charger DC starting battery with electrolyte
12 V charge alternator and starter
Delivered with oil and coolant -30°C
Manual for use and installation
64
415/240 70 88 64 80 122
400/230 70 88 64 80 127
380/220
69 86 62 78
131