Installation Guide

TP-6906 4/16 23Section 1 Installation Instructions
1. Customer connection terminal block. See Figure 1-10 for location. Check the decal on the generator set for terminal block
connections.
2. Connect one end of each cable shield to GROUND at the generator set.
3. See Figure 1-13 for cable specifications.
4. Leave the end of each cable shield disconnected at the last device. If accessory modules are connected, see Section 1.4.9.
Interface Board on the
Model RXT Transfer Switch
Note: Generator set terminal block connections 3 and 4 are NOT USED with the Model RXT ATS.
Generator Set
COM
PWR
B
A
RXT
COM
PWR
B
A
3
GND
RBUS
12VDC
4
4
2
1
Figure 1-11 Model RXT Transfer Switch C ommunication Connection to Generator Set Terminal Block