Brochure

SOCKET STRIPS
7.8
BladePower
®
PizzaPower
®
New:Three Phase – DI-STRIP
®
BladePower
®
PizzaPower
®
A new generation of the power distribution units of the
DI-
STRIP
®
range now ensures even more power: Blade-
Power
®
and PizzaPower
®
for fail-safe power
supply
distribution in network racks.
Increasingly greater packing densities and therefore con-
stantly increasing energy requirements in server racks
caused by blade servers or 1 HU pizza servers will now be
handled electrically.
Up to 35 kW dissipated heat can be removed from modern
CoolTherm
®
server racks. But how is the necessary power
supplied into the rack, which can cause such power
losses?
The PDUs (3x32 A) optimally distribute the required power
over the entire rack, with connection of up to 21 con-
sumers possible at the highest configuration level. 192 A
can be supplied to the rack with redundant feed.
Note
For more information on effective high density
power distribution see
: www.blade-power.com
DOS20153
DI-STRIP
®
BladePower
®
Technical data
- EC 320 sockets (10 A and 16 A).
- Individually fused via thermal circuit breaker
that can be reset in acc. with IEC60934.
- Cable: H05VV-F 5 G 4 mm
2
- Cable: 4 m
- With IEC60309 plug, 1Ph/N/PE 6h blue,
3Ph/N/PE 6h red
Material / Finish
Casing: sheet steel, zinc-plated,
powder-coated
Dimensions
Height: approx. 60 mm
Casing width: 84 mm
Colour
Casing: RAL 9005 black
Approvals
- CE Label in accordance with low voltage
directive 2006/95/EEC
EMC Directive 2006/108/EEC
- Innova GS
- CSA NRTL/C
Load rating
100-240/173-415 Vac
Input: 1x32 A or 3x32 A
Output: 10 A / 16 A
Supply schedule
1 socket strip (PDU)
2 mounting brackets
1 19” mounting bracket
(additional with 19 installation option)
Operating instructions
DI-STRIP
®
Strong points
Cost-conscious
Quick and easy installation on the
server rack’s extrusion.
Costs reduction with regard to
mounting and wiring.
Feed
- Single-phase 32 A and
three-phase 32 A
-
22 kVA
- Ideal for implementing
redundancies (e.g. 192 A)
Crystal clear assignment
Unmistakeable phase assignment
colour-coding (L1, L2, L3).
Installation
Optimum distribution of blade cen-
ter
and pizza server supply with
simple power distribution unit
(PDU)
installation.
Availability
Prevention of “Single Point of
Failure” with individual fusing.
Certification
DOS20155
L S n F1 19“ Plug Model Order no. UP
375 5
•••
BladePower
®
PDU 1x 32 A 03.630.005.1 1 unit
740 15
••
BladePower
®
PDU 3x 32 A 03.630.015.1 1 unit
375 5
••
BladePower
®
PDU 1x 32 A 03.630.805.1 1 unit
740 15
BladePower
®
PDU 3x 32 A 03.630.815.1 1 unit
Dimensions in mm: L = Length, S = Switch, n = Number of sockets,
F1 = Standard side, F2 = Design side, 19”= Suitable for 19” installation, Safe =
Child-safe, HU = Standard height unit, UP = Unit of packaging
= Express item
Conversion: 1 mm = 0.03937 inch 1 kg = 2.2046 pound
Replace .x with the number of the required colour combination:
.1 = RAL 7035, .6 = RAL 7035/RAL 2003