Instruction Manual

TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
Daily check – check LED charge indicator is illuminated
Monthly functional test - simulate a mains supply failure for approx. 30 seconds by
operation of key switch or switching off circuit breaker. Ensure normal supply is restored
after test and ensure charge indicator is illuminated
Annual 3-hour duration test - simulate a mains supply failure for 3-hour continuous test
by operation of key switch or switching off circuit breaker. Ensure normal supply is
restored after test and ensure charge indicator is illuminated
If the luminaire fails any of the above tests, please contact a qualified electrician. See
below for test record sheet