Instruction Manual
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
• Daily check – check LED charge indicator is illuminated
• Monthly functional test - simulate a mains supply failure for approx. 30 seconds by
operation of key switch or switching off circuit breaker. Ensure normal supply is restored
after test and ensure charge indicator is illuminated
• Annual 3-hour duration test - simulate a mains supply failure for 3-hour continuous test
by operation of key switch or switching off circuit breaker. Ensure normal supply is
restored after test and ensure charge indicator is illuminated
• If the luminaire fails any of the above tests, please contact a qualified electrician. See
below for test record sheet