Recommended routine test procedure in accordance with BS5266
Daily check – check LED charge indicator is illuminated
Monthly functional test - simulate a mains supply failure for approx. 30 seconds by operation of key switch
or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is
illuminated
Annual 3-hour duration test - simulate a mains supply failure for 3-hour continuous test by operation of key
switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator
is illuminated
If the luminaire fails any of the above tests, please contact a qualified electrician. See below/overleaf for test
record sheet
TESTING FOR EMERGENCY LUMINAIRES