Instruction Manual

GENERAL
WARNING
This luminaire must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed.
This product contains an LED light source which can be replaced by the end user and a control gear which can
be replaced by a professional.
Ensure the battery is connected via the plug and socket to the emergency inverter
Refasten the LED plate screws
Reattach the diffuser by rotating clockwise
Switch on and check for correct operation, ensuring the green indicator LED is illuminated
We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying
out an emergency duration test
If the batteries have been left in a discharged state for an extended period, we recommend that one or more
charge and discharge cycles are completed which should help to restore the battery capacity
Clean the external surfaces with a damp cloth using a mild solution of detergent and warm water only, do not
use aggressive cleaning products or solvents which may damage the product.
Do not use any source of high-pressure washers to maintain or clean this luminaire.
This product is non-dimmable.