Supply Voltage 24 VAC (+20%/–15%), Class 2
only, 1 VA;
or 24 VDC (+66%/–8%), 50 mA
Input Signals 1 to 5 VDC, 2 to 10 VDC, or
4 to 20 mA
Input Resistance
1 to 5 VDC 100K ohms
2 to 10 VDC 200K ohms
4 to 20 mA 250 ohms
Output Signal 3 to 15 psi (21 to 103 kPa)
Output Capacity 200 scim (55 mL/s)
Main Air
Supply 20 psi nominal (138 kPa)
30 psi maximum (207 kPa)
Consumption 28.8 scim (7.9 mL/s) @ 20 psi
supply (138 kPa)
Manual Override Jumper selectable with po-
tentiometer adj. for 3 to 15 psi
output (XEC-3004 only)
Mounting 2.75" (70 mm) section of 3.25"
(83 mm) Snap Track supplied
for panel mounting and will
t2.75"(70mm)SnapTrack
for horizontal mounting (posi-
tion insensitive)
Material
Plastic Glass-llednylon,ABS
Diaphragms Neoprene
Weight 5.5 ounces (155 grams)
Operating Characteristics
Linearity 1% full scale
Hysteresis & repeatability 0.75% full scale
Connections
Wiring Screw terminals for 14–22
AWG, copper
Air 3/16" (5 mm) nipple for 1/4"
(6 mm) OD polyethylene tub-
ing. 1/8" (3 mm) female NPT
for branch pres sure gauge
Temperature Limits
Operating 40 to 120° F (4 to 49° C)
Shipping –40 to 140° F (–40 to 60° C)
Humidity Non-condensing
Specifications Dimensions and Connectors
All dimensions are in inches (mm).
CAUTION
Pneumatic devices must be supplied with clean, dry
control air. Any other medium (e.g., oil or moisture
contamination) will cause the device to fail.