Product Overview

Features
Choice of tri-state/oating or proportional fail-in-
place or two-position (NO or NC) spring-return
fail-safe
Compact size
Spring-return fail-safe actuators feature easy
manual override, visual position indication, UL
listing for plenum installations, and heat-resistant
lead wires
Non-fail-safe actuators feature manual override
(with 3 mm hex wrench), visual position indica-
tion, and are CE compliant and UL listed
Description 1
Models 1
Features 1
Specifications 2
Accessories/Repair Parts 3
Dimensions 4
Description
These globe zone control valves are designed to
regulate the ow of hot or chilled water to such
applications as VAV terminal unit reheat coils, fan
coil units, and induction units. The compact design
of these units allows easy installation within small
enclosures.
Valve bodies, available in 1/2 to 1" line sizes, are all
normally open. The actuator determines the fail po-
sition. Actuators have position indication and man-
ual override. Replacement actuators can be installed
on the valve bodies without tools.
Specifications and design subject to change without notice.
VEZ-41/42/43 Series
2-Way, NPT, Zone Control Valves (
1
2 to 1")
With Tri-State
or Proportional
Actuator
With 2-Position
Fail-Safe
Actuator
Use this chart to select the desired model of valve:
Models
Actuator
A: 10–0 VDC (closed-open) Proportional (MEP-3516)
B: 0–10 VDC (closed-open) Proportional (MEP-3511)
F: Tri-State, 24 VAC, Floating (MEP-3510)
M: NO, 2-pos., 24 VAC, Spring Return (MEP-3503)
N: NC, 2-pos., 24 VAC, Spring Return (MEP-3501)
P: NO, 2-pos., 120 VAC, Spring Return (MEP-3504)
Q: NC, 2-pos., 120 VAC, Spring Return (MEP-3502)
(NOTE: Actuators “A,” “B,” and “F” are fail-in-place)
Size/Cv
02A: 1/2"; 1.0 Cv
02B: 1/2"; 2.5 Cv
02C: 1/2"; 4.0 Cv
03A: 3/4"; 4.1 Cv
04A: 1"; 7.0 Cv
Control Type
1: Normally Open (actuator “M” or “P” only)
2: Normally Closed (actuator “N” or “Q” only)
3: Fail in Place (actuator “A,” “B,” or “F” only)
VEZ-4 X YYY MB Z