Owner manual
THE-1105 2 Installation Guide
© 2013 KMC Controls, Inc. 870-019-01G
KMC Controls, Inc.
19476IndustrialDrive
NewParis,IN46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
Important Notices
Thematerialinthisdocumentisforinformation
purposesonly.The contents and the product it de-
scribes are subject to change without notice. KMC
Controls, Inc. makes no representations or warran-
ties with respect to this document.Innoeventshall
KMCControls,Inc.beliableforanydamages,direct
orincidental,arisingoutoforrelatedtotheuseof
thisdocument.
Wiring
Maintenance
Carefulinstallationwillalsoensurelong-term
reliabilityandperformance.Removedustasneces-
saryfromholesintopandboom.Cleanwithaso,
dampclothandmildsoap.
More Information
Forcontroller/sowarecongura-
tionforthehumidity input,see
therelevantdocumentationfor
thecontrollerandsoware.For
controller/sowareconguration
forthethermistor inputaswellas
mountingconsiderations,trouble-
shooting,andotherinformation,
seealsotherelevantsectionsinthe
STE-6010/6011/6013/6015 Room
Temperature Sensors Application
Guide.
Forspecicationsandaccessory
information,seetheTHE-1105
Data Sheet.
CAUTION
Excess wire inside the THE-1105 may cause
damage to the thermistor. Be careful when
wiring and replacing the unit’s cover.
CAUTION
Use only a 24 VAC, Class 2 transformer for
power.
NOTE: Use18–22AWGstrandedwirewitha
maximumlengthof250feet.
1. Connectthe24VAC(–15%/+20%,Class2ONLY)
transformer,carefullyobservingthephasing.(See
thewiringdiagram.)
2. Connectthehumiditytransmieroutput,
selectingeither0to10VDCandSignalGroundor
0to5VDCandSignalGround.
3. Connectthetemperaturesensor(TypeII10K
thermistor)ifrequired.