User guide

THE-1002 2 Installation Guide
© 2013 KMC Controls, Inc. 859-019-01I
KMC Controls, Inc.
19476IndustrialDrive
NewParis,IN46553
574.831.5250
www.kmccontrols.com;info@kmccontrols.com
Important Notices
Thematerialinthisdocumentisforinformation
purposesonly. The contents and the product it de-
scribes are subject to change without notice. KMC
Controls, Inc. makes no representations or warran-
ties with respect to this document.Innoeventshall
KMCControls,Inc.beliableforanydamages,direct
orincidental,arisingoutoforrelatedtotheuseof
thisdocument.
Maintenance
Carefulinstallationwillalsoensurelong-termreli-
abilityandperformance.Removedustasnecessary
fromthesensingtube.
More Information
Forcontrollerconguration
ofthehumidity input,see
therelevantdocumenta-
tionforthecontrollerand
soware.Forcontroller
congurationofthe
thermistor inputaswellas
mountingconsiderations,
troubleshooting,andother
information,seealsothe
relevantsectionsinthe
STE-6010/6011/6013/6015
Application Guide.
ForTHE-102specications
andaccessoryinformation,
seetheTHE-1002 Data
Sheet.
Wiring
Relay
Module
24 VAC
To
Probe
Cable from Humidity
Sensor in Probe
(Do NOT attempt to
shorten or lengthen
this ribbon cable)
10K Ohm
Thermistor Leads
24 VAC
0-5
VDC
0-10
VDC
4-20
mA
Controller
Temperature Input
Signal Ground
Humidity Input*
*Load between Humidity Input and Signal Ground
is 250 ohms min. to 650 ohms max. for 4-20 mA
or 1000 ohms min. for VDC
PhaseNeutral
Forpower,connecta24VAC,Class2only,trans-
former(seethediagram).
Connectthedesiredhumidityoutput(0–5VDC,0–10
VDC,or4–20mA)fromtheTHE-1002tothecontrol-
lershumidityinput.(Setthecontrollerspull-up
resistoraccordingly.)
NOTE: Thethermistorandthehumidityoutput
haveacommonoutputsignalground.
Connectthetemperatureoutput(thermistorleads)
fromtheTHE-1002tothecontrollerstemperature
input.Makewireconnectionswitheitherbu-splices
orsolder.Usingwirenutsisnotrecommended.(Set
thecontrollerspull-upresistoraccordingly.)
NOTE: Thetwo-wirethermistorleadsarepolarity
insensitive.
NOTE: Therelaymodulemountedinsidethe
electricalhousingishard-wiredtothe
sensingprobe. Do not aempt to lengthen
or shorten the prewired ribbon cable.