Product Overview
Table Of Contents
1
Description and Application
The KMC SSS-1000 series sensors are designed to
sense dierential pressure in the inlet section of VAV
(Variable Air Volume) terminal units and fan termi-
nal units. These sensors are most typically used in
conjunction with VAV controllers for individual zone
control in HVAC systems. They can also be used to
sense dierential pressure at other locations in the
main or branch duct systems. The dierential pres-
sure read between the high “H” port and the low
“L” port can be used to determine the air ow. Static
pressure can also be measured using just one of the
ports with the sensor rotated 90°. (See Sample Ap-
plications on page 4.)
Models oer up to four sensing points and sensing
lengths of 3-5/32 to 9-29/32 inches to accommodate
box size diameters of 4 to 16 inches.
For using SSS-100x sensors with CSC-3000 series,
CSP-4000/5000 series, KMD-7000 series, and BAC-
7000/8000/9000 series controllers, use a barb union
adapter and appropriately sized polyethylene tubing
to the sensor and controller. For maximum accuracy
in the CSP-5000 series, KMD-7000 series, and BAC-
7000 series controllers, the 3/8" OD tubing between
the sensor and the adapter should be as short as
possible, and the 1/4" OD tubing from the adapter to
the controller should be 24" long (on both the High
and the Low sides). Alternately, use the equivalent
SSS-101x sensor and just 1/4" OD tubing (no adapter
is necessary).
To nd the appropriate sensor “K” factor:
• For VAV controllers needing K
CFM
for setup, see
“Cubic Feet Per Minute” K Factors on page 2.
• For VAV controllers needing K
FPM
for setup, see
“Feet Per Minute” K Factors on page 3.
See the controller’s documentation for details.
Specifications and design subject to change without notice.
SSS-1000 Series
Differential Pressure Flow Sensors
Models
SSS-100x (light gray) models have 1/4" connections
for 3/8" OD polyethylene tubing
SSS-1002 One sensing point, 3-5/32"
(80 mm) length
SSS-1003 Two sensing points, 5-13/32"
(137 mm) length
SSS-1004 Three sensing points, 7-21/32"
(195 mm) length
SSS-1005 Four sensing points, 9-29/32"
(252 mm) length
SSS-101x (light almond) models have 3/16"
connections for 1/4" OD polyethylene tubing
SSS-1012 One sensing point, 3-5/32"
(80 mm) length
SSS-1013 Two sensing points, 5-13/32"
(137 mm) length
SSS-1014 Three sensing points, 7-21/32"
(195 mm) length
SSS-1015 Four sensing points, 9-29/32"
(252 mm) length
NOTE: For maximum measurement accuracy,
install the longest sensor that will t in
the duct.
Description and Application 1
Models 1
Dimensions and Details 2
Specifications 2
General 2
“Cubic Feet Per Minute” K Factors 2
“Feet Per Minute” K Factors 3
Sample Applications 4
Differential Pressure Sensor for Pressure Independent VAV 4
Static Pressure Sensor for Static Pressure Bypass Control 4