Product Overview

Description and Application
The KMC SSS-1000 sensors are designed to sense
dierential pressure in the inlet section of VAV (Vari-
able Air Volume) terminal units and fan terminal
units. They can also be used to sense dierential
pressure at other locations in the main or branch
duct systems. The dierential pressure read between
the high “H” port and the low “L” port can be used
to determine the air ow. Static pressure can also be
measured using just one of the ports rotated 90°. (See
Sample Applications on page 4.)
Models oer up to four sensing points and sensing
lengths of 3-5/32 to 9-29/32 inches to accommodate
box size diameters of 4 to 16 inches.
These sensors are typically used in conjunction
with the CSC-1000/2000/3000 series, CSP-4000/5000
series, KMD-7000 series, and BAC-7000 series of
VAV controllers for individual zone control in HVAC
systems.
For using SSS-100x sensors with CSC-3000 series,
CSP-4000/5000 series, KMD-7000 series, and BAC-
7000 series controllers, use a 3/8" to 1/4" barb union
adapter and appropriate polyethylene tubing to the
sensor and controller. For maximum accuracy in the
CSP-5000 series, KMD-7000 series, and BAC-7000
series controllers, the 3/8" OD tubing between the
sensor and the adapter should be as short as pos-
sible, and the 1/4" OD tubing from the adapter to
the controller should be 24" long (on both the High
and the Low sides). OR use the equivalent SSS-101x
sensor.
To nd the appropriate sensor “K” factor:
For digital VAV controllers needing K
CFM
for
setup, see “Cubic Feet Per Minute” K Factors on
page 2.
For CSC-2000 series, CSC-3000 series, and CSP-
4000 series controllers (needing K
FPM
for setup),
see “Feet Per Minute” K Factors on page 3.
For CSP-5000, KMD-7000, and BAC-7000 series
that operate dierently—see their respective in-
stallation guides and application guides for more
information.
Specifications and design subject to change without notice.
SSS-1000 Series
Differential Pressure Flow Sensors
Models
SSS-100x (light gray) models have 1/4" connections
for 3/8" OD polyethylene tubing
SSS-1002* One sensing point, 3-5/32"
(80 mm) length
SSS-1003 Two sensing points, 5-13/32"
(137 mm) length
SSS-1004 Three sensing points, 7-21/32"
(195 mm) length
SSS-1005 Four sensing points, 9-29/32"
(252 mm) length
*NOTE: KIT-8001 includes an SSS-1002, two barb
union adapters, two 1.5" lengths of 1/4"
tubing, and two 36" lengths of 3/8 tubing.
SSS-101x (light almond) models have 3/16"
connections for 1/4" OD polyethylene tubing
SSS-1012 One sensing point, 3-5/32"
(80 mm) length
SSS-1013 Two sensing points, 5-13/32"
(137 mm) length
SSS-1014 Three sensing points, 7-21/32"
(195 mm) length
SSS-1015 Four sensing points, 9-29/32"
(252 mm) length
NOTE: For maximum measurement accuracy,
install the longest sensor that will t in
the duct.
Description and Application 1
Models 1
Dimensions and Details 2
Specifications 2
General 2
“Cubic Feet Per Minute” K Factors 2
“Feet Per Minute” K Factors 3
Sample Applications 4
Differential Pressure Sensor for Pressure Independent VAV 4
Static Pressure Sensor for Static Pressure Bypass Control 4

Summary of content (4 pages)