SAE-1101/1102/1151/1152 Carbon Monoxide (CO) Detectors 4 Installation Guide
Normal (Configuration) Menu
PressandreleasetheMENUbuontoenterthe
congurationmenu:
1. BUZZER TRIP=150: The factory default for the
buzzer trip level is 150 ppm. This can be changed
by using the ROLL buon from 100 to 400 ppm
in increments of 10 ppm. Use the SAVE buon to
save any change to memory.
PresstheMENUbuon.
2. BUZZER DEL=5MIN: The factory default is 5
minutes and this can be changed with the ROLL
buon to 0, 1, 2, 3, 4 or 5 minutes. Use the SAVE
buon to save any changes to memory.
PresstheMENUbuon.
3. BUZZER ENABLE: The factory default is
ENABLE. It can be changed to DISABLE with the
ROLL buon. Use SAVE to save any changes to
memory. If this is set to DISABLE the buzzer will
never sound.
PresstheMENUbuon.
4. RELAY1 TRIP=50: The factory default Relay1 trip
level is 50 ppm. Use the ROLL buon to change it
to 25 or to 40–350 ppm in increments of 10 ppm.
The SAVE buon saves any changes.
PresstheMENUbuon.
5. RELAY1 HYST=10: The factory default for Relay1
hysteresis (deadband) is 10 ppm. Change using
the ROLL buon to 10, 15, 25, 50, or 75 ppm. Save
using the SAVE buon.
NOTE: RELAY1 HYST is always less than RELAY1
TRIP and may not display all options.
PresstheMENUbuon.
6. RELAY1 DEL=2MIN: The factory default is 2
minutes and this can be changed with the ROLL
buon to 0, 1, 2, 3, 4, or 5 minutes. Save using the
SAVE buon.
PresstheMENUbuon.
7. RELAY2 TRIP=150: The factory default Relay2
trip level is 150 ppm. Use the ROLL buon to
change it to 100–400 ppm in increments of 10
ppm. The SAVE buon saves any changes.
PresstheMENUbuon.
8. RELAY2 HYST=25: The factory default for Relay2
hysteresis (deadband) is 25 ppm. Change using
the ROLL buon to 10, 15, 25, 50, or 75 ppm. Save
using the SAVE buon.
PresstheMENUbuon.
9. RELAY2 DEL=2MIN: The factory default is 2
minutes and this can be changed with the ROLL
buon to 0, 1, 2, 3, 4, or 5 minutes. Save using the
SAVE buon.
PresstheMENUbuon.Returns to normal
operation.
Test Menu
1. OUTPUT TEST 4mA/0V: This item tests the
analog output (current or voltage depending on
the jumper position). Use the ROLL buon to
change the output signal to 4, 8, 12, 16, or 20 mA
or 0, 1, 2, 3, 4, or 5 VDC.
NOTE: If 10 VDC output is selected by jumpers, the
output voltage will be double the display.
PresstheMENUbuon.
2. BUZZER TEST OFF: If installed, use the ROLL
buon to turn the buzzer ON or OFF. Use SAVE
to exit the menu.
PresstheMENUbuon.
3. RELAY1 TEST OFF: If installed, use the ROLL
buon to turn the relay ON or OFF. Use SAVE to
exit the menu.
PresstheMENUbuon.
4. RELAY2 TEST OFF: If installed, use the ROLL
buon to turn the relay ON or OFF. Use SAVE to
exit the menu.
PresstheMENUbuon.Returns to normal
operation.
Calibration Menu
1. SENSOR (ECON300): The sensor type and range
are indicated on the LCD. Do not change this
seing.
PresstheMENUbuon.
2a. CALIBRAT 20mA x: If set for current output,
this item allows calibration of the 20 mA output
signal. Connect a meter to the output and use the
ROLL buon to set the output to exactly 20.0 mA.
Use the SAVE buon to save any change.
PresstheMENUbuon.
2b. CALIBRAT 5V x: If set for current output, this
item allows calibration of the 5 VDC output
signal. Be sure the 5VDC output jumper positions
are selected, connect a meter to the output, and
use the ROLL buon to set the output to exactly
5.0 VDC. Save using the SAVE buon.
PresstheMENUbuon.
3. RESTORE DEFAULTS: Press the SAVE buon
here to restore all factory defaults to their original
seings as when shipped from the factory.
PresstheMENUbuon.Returns to normal
operation.