Maintenance
No routine maintenance is required, however protec-
tion from extremes of humidity and dirt is recom-
mended. Careful installation will also ensure long
term reliability and performance.
NOTE: For more information
about this CSP-5001
and CTE-5101 example,
see the CSP-5001/5002
VAV Flow Controller-
Actuators Application
Guide.
NOTE: Triacoutputsarefor24
VACloadsonly.
NOTE: Thephasesideofthe
transformerconnects
tothe“common”
sideoftheload
(contactors).
Stage Status
Normal Triac Voltage (Approximate, and With Load)
Across Load
(Terminal ~/Phase to
Terminal Fan, 1, or 2)
Across Triac
(Terminal –/Neutral to
Terminal Fan, 1, or 2)
On 24 VAC 1 VAC
Off 0 VAC 24 VAC
Troubleshooting
• Check the wiring.
• Check the voltage from the thermostat/control-
ler (measured from Terminal T to Terminal –/
Neutral). (See the voltage charts above and on the
previous page.)
• Check the voltage across the triac and load. (See
the chart below.)