User guide
Wiring
Installation Guide
Relay Module, 3 Stage, Reheat
REE-4001
Mounting
Connect as shown in the sample illustration on the
next page. Supply the relay with 24 VAC, +20%/
–15%. (Use wire size of 14 to 22 AWG, stranded.)
NOT
E: The“C”terminalontheserelaysdoes
NOTdenoteACCommon/Neutral!“C”
isconnectedtothePHASEsideofthe24
VAC(andthephasesideiswherethethree
contactorsareconnectedin“common”).
“9”istheneutralside.
NOTE: Triacstages1through3arefor24VAC
loadsonly.
Check the graph for thermostat signal setpoints and
corresponding stages. Stage 1 turns on at 2 VDC,
Stage 2 at 4 VDC, and Stage 3 at 6 VDC. There is a
0.33 VDC switching dierential on each stage.
The REE-4001 may be mounted directly to a control
box surface or in a 2 x 4" electrical handy box. Add a
blank cover to conceal the module if desired.
Mounting 1
Wiring 1
Troubleshooting 2
Maintenance 2
Important Notices 2
REE-4001 Installation Guide