Product Overview
Description and Application
The RCC-1111 multiple input selector relay is de-
signed for selection of the lowest and/or highest of 6
dierent pneumatic inputs.
It is a restricted device designed for pilot-duty
operation. If a large output volume is required, use
a volume booster relay. For applications requiring a
“low” output, the integral selector valve must be set
for the correct number of inputs. If a “high” output
is required, this dial does not need be set.
The RCC-1111 can be mounted in-line or by using
the included right-angle bracket.
Features
◆ Designed for pilot-duty operation
◆ Selects the lowest and/or highest of up to 6 dier-
ent pneumatic inputs
◆ May be mounted in-line or with a right-angle
bracket
RCC-1111
Multiple Input, High and Low
Pressure Selector Relay
Specifications
Supply Pressure 20 psig (138 kPa)
30 psig (207 kPa) maximum
Air Consumption 28.8 scim (7.85 mL/s)
Connection
3/16" (5 mm) nipple for 1/4" (6
mm) OD polyethylene tubing
Material
Flame-retardant plastic
Weight 3.5 oz. (99 grams)
Temperature Limits
Operating 40 to 120° F (4 to 29° C)
Shipping –40 to 140° F (–40 to 60° C)
Dimensions and Details
All dimension are
in inches (mm)
CAUTION
Pneumatic devices must be supplied with clean, dry
control air. Any other medium (e.g., oil or moisture
contamination) will cause the device to fail.
KMC Controls, Inc.
19476 Industrial Drive, New Paris, IN 46553
574.831.5250
www.kmccontrols.com; info@kmccontrols.com
© 2010 KMC Controls, Inc. 109-035-01C