Product Overview

© 2013 KMC Controls, Inc. 100-035-01G
KMC Controls, Inc.
19476 Industrial Drive, New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
Details
All dimension are in inches (mm)
Main air is Port M, output is Port B, input is Port S.
Main air is Port M and output is Port B. Inputs to be averaged are applied to S1 and S2.
The output, Port B, is the lower of the two input pressures applied to Ports S1 and S2. Take
CARE when applying “one-pipe” restricted signals to S2 since the relay’s output is derived
from the air applied to S2.
No adjustments need to be made. The design allows for positive switching between signals,
and the non-transmitted signal is internally blocked. The signals applied to Ports S1 and S2
must come from “relieving” type devices. DO NOT supply from NO or NC ports of diverting
relays or solenoid air valves.
The setpoint dial can be rotated within the body to adjust the switching point. One turn yields
approximately 6 psi change in the switching point. Each unit is factory-set to switch between
18 and 23 psi, which allows it to match most two-pressure main air systems. This device is not
“snap-acting” (it must receive a positive pressure change at its signal port to switch).
Specifications
Supply Pressure 0–20 psi (138 kPa) operating
30 psi (207 kPa) maximum
Air Capacity
RCC-1001/1012/1101/1112 17.3 scim (4.7 mL/s) @ 20
psi (138 kPa)
RCC-1006/1106 21.6 scim (5.9 mL/s) @ 20 psi
(138 kPa)
RCC-1009/1109 432 scim (117.9 mL/s) @ 20 psi
(138 kPa)
RCC-1008/1108 260 scim (70.6 mL/s) @ 5 psi
(34.5 kPa) pressure drop
Air Consumption
RCC-1001/1012/ 1101/1112 17.3 scim (4.7 mL/s)
RCC-1006/1106 0–21.6 scim (5.9 mL/s) on Port S2
RCC-1008/1108/1009/1109 None
RCC-1013 14.4 scim (3.9 mL/s)
RCC-1102 17.3 scim (4.7 mL/s) on Main,
0 on Signal
Bias Adjustment
RCC-1001/1012/1101/1112 +/15 psi (103 kPa)
Switching and Setpoint (RCC-1009/1109 Only)
Factory Setpoint 18–23 psi (124–159 kPa)
Setpoint Range 3–23 psi (21–159 kPa)
Switching Dierential 5 psi (34 kPa)
Action C and NO connected below
setpoint, C and NC connected
above setpoint
Supply Connection 3/16" (5 mm) for 1/4" (6 mm)
O.D. polyethylene tubing
Weight 2.5 oz. (71 grams) maximum
Material RCC-1009/1109 are glass-lled
nylon, all other models are
beige ame-retardant plastic
Temperature Limits
Operating 40 to 120° F (4 to 49° C)
Shipping –40 to 140° F (–40 to 60° C)
Main air is Port M and output is Port B. The input signal to be repeated is connected to Port S.