Product Overview
Table Of Contents
© 2013 KMC Controls, Inc.  100-035-01G
KMC Controls, Inc.
19476 Industrial Drive, New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
Details
All dimension are in inches (mm)
Main air is Port M, output is Port B, input is Port S.
Main air is Port M and output is Port B. Inputs to be averaged are applied to S1 and S2.
The output, Port B, is the lower of the two input pressures applied to Ports S1 and S2. Take 
CARE when applying “one-pipe” restricted signals to S2 since the relay’s output is derived 
from the air applied to S2.
No adjustments need to be made. The design allows for positive switching between signals, 
and the non-transmitted signal is internally blocked. The signals applied to Ports S1 and S2 
must come from “relieving” type devices. DO NOT supply from NO or NC ports of diverting 
relays or solenoid air valves.
The setpoint dial can be rotated within the body to adjust the switching point. One turn yields 
approximately 6 psi change in the switching point. Each unit is factory-set to switch between 
18 and 23 psi, which allows it to match most two-pressure main air systems. This device is not 
“snap-acting” (it must receive a positive pressure change at its signal port to switch). 
Specifications
Supply Pressure  0–20 psi (138 kPa) operating 
30 psi (207 kPa) maximum
Air Capacity
RCC-1001/1012/1101/1112 17.3 scim (4.7 mL/s) @ 20 
psi (138 kPa)
RCC-1006/1106  21.6 scim (5.9 mL/s) @ 20 psi 
(138 kPa)
RCC-1009/1109  432 scim (117.9 mL/s) @ 20 psi 
(138 kPa)
RCC-1008/1108  260 scim (70.6 mL/s) @ 5 psi 
(34.5 kPa) pressure drop
Air Consumption
RCC-1001/1012/ 1101/1112 17.3 scim (4.7 mL/s)
RCC-1006/1106  0–21.6 scim (5.9 mL/s) on Port S2
RCC-1008/1108/1009/1109 None
RCC-1013  14.4 scim (3.9 mL/s)
RCC-1102  17.3 scim (4.7 mL/s) on Main, 
0 on Signal
Bias Adjustment
RCC-1001/1012/1101/1112 +/–15 psi (103 kPa)
Switching and Setpoint (RCC-1009/1109 Only)
Factory Setpoint  18–23 psi (124–159 kPa)
Setpoint Range  3–23 psi (21–159 kPa)
Switching Dierential 5 psi (34 kPa)
Action  C and NO connected below 
setpoint, C and NC connected 
above setpoint
Supply Connection  3/16" (5 mm) for 1/4" (6 mm) 
O.D. polyethylene tubing
Weight  2.5 oz. (71 grams) maximum
Material  RCC-1009/1109 are glass-lled 
nylon, all other models are 
beige ame-retardant plastic
Temperature Limits
Operating  40 to 120° F (4 to 49° C)
Shipping  –40 to 140° F (–40 to 60° C)
Main air is Port M and output is Port B. The input signal to be repeated is connected to Port S.