Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Barber Colman TP-81xx Thermostats Replacement Applications 57 CTE-5202 Applications Guide, AN0912A Rev. H
TP-8124/8125 Replacement with One or No MP-52xx Actuators
Select
Sequence
3
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
Red (+20 VDC)
Yellow (IV1)
Blue (Common)
(Tape Red Leads
if Present)
Red (+20 VDC)
Controlled Device
with
Power Supply
Yellow (IV1)
Blue (Common)
Red (+20 VDC)
Controlled Device
with
Power Supply
Yellow (IV–)
Blue (Common)
MP-52xx Series
Actuator (or Other
Controlled Device
with Power Supply)
Red (+20 VDC)
Controlled Device
with
Power Supply
Yellow (IV–)
Blue (Common)
(Tape Red Leads
if Present)
CTE-5202 thermostats can replace TP-8101/8102/8103
thermostats and use the 20 VDC supplied by a
controlled device. (For more information, see the
manufacturer’s installation guide for the controlled
devices.)
CAUTION
Never connect together the red leads (or +20
VDC terminals) of controlled devices with
internal power supplies (with the exception of
MP-52xx actuators).
AO2 MAX
AO2 MIN
AO2 (RA)
AO1 (DA)
AO1 MIN
AO1 MAX
Cooling
Setpoint
Heating
Setpoint
Temp.
Increasing
2° F 2° F
Select Sequence 3 (from the CTE-5202 SYSTEM
menu). See Change Conguration on page 6.