Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Barber Colman TP-81xx Thermostats Replacement Applications 54 CTE-5202 Applications Guide, AN0912A Rev. H
Barber Colman TP-81xx Thermostats
Replacement Applications
This section gives sample applications for using the
CTE-5202 in the place of a Barber Colman (TAC,
Invensys, Schneider Electric) TP-81xx thermostat.
Some of the applications include use with MP-52xx
“beer can” actuators.
TP-8101, TP-8102,
and TP-8103 Leads
and Terminals
Function CTE-5202 Terminals
Red Wire Lead +20 VDC
~ (Phase)
Yellow Wire Lead
Proportional
Output
AO1
Blue Wire Lead Common
T
(Common)
Terminal 1 Common
T
(Common)
Terminal 2 Auxiliary Input AI1
NOTE: Use Sequence 1. See sample applications on page 55 and
page 56.
TP-8124 and
TP-8125 Terminals
Function
CTE-5202
Terminals
OP2 2–15 VDC Cooling (DA) AO1
+20 +20 VDC (Input)
~ (Phase)
OP1 15–2 VDC Heating (RA) AO2
Com Common
T
(Common)
NOTE: Use Sequence 3. See sample applications on page 57 and
page 58.