Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Pressure Independent VAV Applications with CEP/CSP-4000 Series 52 CTE-5202 Applications Guide, AN0912A Rev. H
Dual Duct Heating and Cooling VAV
Dual duct applications connect two CEP-4000 series
controllers, mounted separately on the hot and cold
air-duct dampers, with each controller using its own
ow sensor.
The hot deck controller receives its requested ow
signal from AO2 on the CTE-5202, while the cold
deck uses the AO1 signal. Both controllers can be
set independently for minimum and maximum ow
seings.
Sequence 3 should be selected from the CTE-5202
SYSTEM menu. See Change Conguration on page 6.
(See also the (Dual Duct) Heating and Cooling VAV
section with a CTE-1103 in the CEP-4000 Series
Applications Guide.)
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
24 VAC @ 20 VA
~
–
(Phase)
(Neutral)
1
2
3
7
6
5
4
3
2
1
8
9
10
11
12
13
14
CEP-4xxx
Controller-Actuator
SSE-1001/1002
Flow Sensor
1
2
3
7
6
5
4
3
2
1
8
9
10
11
12
13
14
SSE-1001/1002
Flow Sensor
CEP-4xxx
Controller-Actuator
(Hot Deck)
(Cold Deck)
Select Sequence 3
Cooling Max.
Cooling
Min.
0 fpm
(Colder Room Temperature Warmer)
3000
fpm
Air
Flow
Min.–3000 fpm
0–3000
fpm
Heating Max.
Min.–3000 fpm
Cooling SetpointHeating Setpoint
Minimum Air from Cooling
Cooling Max.
Cooling
Min.
0 fpm
(Colder Room Temperature Warmer)
3000
fpm
Air
Flow
Min.–3000 fpm
0–3000
fpm
Heating Max.
Min.–3000 fpm
Cooling SetpointHeating Setpoint
Minimum Air from Cooling
Cooling Max.
Cooling
Min.
0 fpm
(Colder Room Temperature Warmer)
3000
fpm
Air
Flow
Min.–3000 fpm
0–3000
fpm
Heating Max.
Min.–3000 fpm
Cooling SetpointHeating Setpoint
Minimum Air from Heating