Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Pressure Independent VAV Applications with CEP/CSP-4000 Series 46 CTE-5202 Applications Guide, AN0912A Rev. H
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
24 VAC @ 10 VA
~
–
(Phase)
(Neutral)
7
6
5
4
3
2
1
8
9
10
11
12
13
14
CEP-4xxx
Controller-Actuator
SSE-2001/2002
Flow Sensor
SPDT Relay
1
2
3
Y
X
Select Sequence 1
Using the thermistor in an SSE-2001/2002 sensor
enables the sensing of morning warm-up, and
adding a SPDT relay or switch enables overriding
the air ow to fully open for morning warm-up.
Otherwise the example below is the same as the
conguration in Cooling on page 45.
The SPDT relay selects one of the two modes (Auto
or Fully Open). Terminal 6 on the CEP-4xxx is
connected to either Terminal 5 (Fully Open) or to AO1
on the CTE-5202 (Auto, the default). When Terminal
6 is connected to Terminal 5, the 9.1 VDC causes full
ow.
(See also the Cooling with Morning Warm-Up section
in the CEP-4000 Series Applications Guide.)
Cooling with Morning Warm-Up
2° F
2° F
2° F
COLD AIR SEQUENCE
AO1 (DA)
Setpoint
AO1 MIN
HOT AIR SEQUENCE (Morning Warm Up)
AO1 (RA)
AO1 MAX
AO1 MAX
AO1 MIN
Temp. Increasing
Setpoint