Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Pressure Independent VAV Applications with CEP/CSP-4000 Series 45 CTE-5202 Applications Guide, AN0912A Rev. H
Cooling
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
24 VAC @ 10 VA
~
–
(Phase)
(Neutral)
1
2
3
7
6
5
4
3
2
1
8
9
10
11
12
13
14
CEP-4xxx
Controller-Actuator
SSE-1001/1002
Flow Sensor
Cooling Max.
Cooling Min.
0 fpm
Setpoint
(Colder Room Temperature Warmer)
3000
fpm
Air
Flow
Min.3000 fpm
03000 fpm
CTE-5202 thermostats can use CEP/CSP-4000 series
electronic VAV controllers to operate damper boxes
in a pressure-independent VAV system. As shown
in the diagram, a “requested ow” voltage signal
(AO1) is connected to the CEP-4xxx to adjust airow
from minimum to maximum ow according to
space demand. Minimum and maximum ow limit
adjustments can be made at the thermostat or at the
controller.
Select Sequence 1 (from the CTE-5202 SYSTEM
menu). See Change Conguration on page 6. (This
replaces a CTE-1001/1101/5001/5011 with Direct
Acting reset.)
(See also the Cooling section in the CEP-4000 Series
Applications Guide.)
Select Sequence 1