Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Pressure Independent VAV Applications with CSP-5001/5002 35 CTE-5202 Applications Guide, AN0912A Rev. H
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
CSP-5001
Controller-Actuator
H
~
16
V
DC
I
N
O
U
T
––
L
24 VAC
REE-5001 Relay Module
~
–
24 VAC
3 2 1
Stages
3-Stage Reheat
T
(To Flow Sensor)
24 VAC @ 34 VA
~
–
24 VAC Contactors
(10 VA Max. per Stage)
2
1
3
Load
(Phase)
(Neutral)
Select Sequence 2,
with or without
Auxiliary Flow
Cooling with 3-Stage Reheat
This application uses a CSP-5001 along with an
REE-5001 relay module and three 24 VAC contactors
for three stages of reheat.
As the temperature drops below setpoint, the rst
stage of reheat begins. As the temperature continues
to drop, the second stage and later the third stage
begin as needed.
Select Sequence 2 (from the CTE-5202 SYSTEM
menu), with or without Auxiliary Flow (AO1 AUX
in LIMITS menu). See Change Conguration on
page 6.
(See also the Cooling with 3-Stage Reheat section
with a CTE-5104 for auxiliary ow or a CTE-5103
without auxiliary ow in the CSP-5001/5002 Appli-
cations Guide.)
NOTE: Triac outputs on
the REE-5001
are for 24 VAC
loads only. The
phase side of
the transformer
connects to
the “common”
side of the load
(contactors).
NOTE: See also the REE-
5001 Installation
Guide.
2° F
Of Loop
10%
2° F
AO1 MAX
AUX
AO1 MIN
COLD AIR SEQUENCE
0 Volts
12 Volts
Temp. Increasing
Cooling
Setpoint
Heating
Setpoint
9.5 V
3.5 V
#3
#1
6.5 V
#2
Reheat
Stages
AO2 (RA)
AO1 (DA)