Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Pressure Independent VAV Applications with CSP-4702 29 CTE-5202 Applications Guide, AN0912A Rev. H
Cooling with Hot Water Reheat
See Cooling with 3-Stage Reheat on page 24. This
application operates the same except for using a hot
water valve instead of electric heating elements for
reheat (a VEB-43/46 series valve in place of the REE-
5001 relay).
AO1 controls airow and AO2 controls the valve.
When there is a call for heat, the thermostat
modulates the hot water valve.
Select
Sequence 2
2° F
Of Loop
10%
2° F
AO1 MAX
AUX
AO1 MIN
COLD AIR SEQUENCE
0 Volts
12 Volts
Temp. Increasing
Cooling
Setpoint
Heating
Setpoint
Hot Water Reheat
AO2 (RA)
AO1 (DA)
MEP-4002
Actuator on
VEB-43/46
Series
Valve
24 VAC
Common
Input
Out
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
~
–
(Phase)
(Neutral)
(To Flow Sensor)
CSP-4702
Controller-Actuator
24 VAC @ 10 VA