Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Pressure Independent VAV Applications with CSP-4702 25 CTE-5202 Applications Guide, AN0912A Rev. H
Cooling with 3-Stage Reheat and Night Setback/Setup
This conguration is the same as on the previous
page except for the addition of an SPST relay or
switch.
See Cooling with 3-Stage Reheat on page
24.
The switch or relay is driven by a night/unoccupied
setback/setup signal from other equipment not
shown. When the contact is closed (e.g., by a timer),
setback/setup mode initiates, changing the setpoint
by the oset selected in ADVANCE > SETBACK
menu. See Change Conguration on page 6 and
Unoccupied/Standby Setback on page 5.
NOTE: The night/unoccupied setback oset does
not apply to morning warm-up.
NOTE: This conguration requires the system fan
to be on during setback/setup mode.
NOTE: Triac outputs on the REE-5001 are for 24
VAC loads only. The phase side of the
transformer connects to the “common” side
of the load (contactors).
NOTE: See also the REE-5001 Installation Guide.
Select Sequence 2,
with or without
Auxiliary Flow
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
~
–
(Phase)
(Neutral)
(To Flow Sensor)
REE-5001 Relay Module
~
–
24 VAC
3 2 1
Stages
3-Stage Reheat
T
24 VAC Contactors
(10 VA Max. per Stage)
2
1
3
Load
SPST
Relay
CSP-4702
Controller-Actuator
24 VAC @ 35 VA