Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Pressure Independent VAV Applications with CSP-4702 20 CTE-5202 Applications Guide, AN0912A Rev. H
Replacing a CSP-5001/5002
The CSP-4702 can be used in any of the CSP-
5001/5002 applications shown in the section Pressure
Independent VAV Applications with CSP-5001/5002
on page 32. However, there are some dierences
among the models of which the installer must be
aware:
• Output torque of the CSP-4702 is 40 in. lb.
instead of the CSP-500x’s 50 in. lb. Check torque
requirements of the damper when replacing a
CSP-500x.
• Factory-set rotation direction of the CSP-4702
is CCW to close and CW to open, the same as
the CSP-5001. The direction can be reversed by
changing the position of a jumper.
• If a CSP-4702 is used to replace an existing
CSP-500x and limits were set in the CSP-500x,
the limits will need to be set (in either the CSP-
4702 or the thermostat). If a CSP-4702 is used to
replace an existing CSP-500x and limits were set
in the thermostat, the limits in the thermostat
should be checked and adjusted to ensure ac-
curacy.
• The terminals on the CSP-4702 terminal strips
are in a dierent order than on a CSP-500x.
• “Override to Fully Closed” shown in Auto and
Override (to Fully Closed or Fully Open) on page
34 will not work as described with the CSP-4702.
See the Operation Test section of the CSP-4702
Installation Guide.
NOTE: Compare the wiring of the CSP-4702
version of cooling with heating changeover
below to the CSP-5001 version in Cooling
with Heating Changeover on page 37. See
also Cooling with Heating Changeover on
page 26.
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
~
–
(Phase)
(Neutral)
1
2
3
TTE-2001 or STE-140x
Duct Temp. Sensor
(To Flow Sensor)
CSP-4702
Controller-Actuator
24 VAC @ 5 VA