Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Pressure Dependent VAV Applications with MEP-4002 18 CTE-5202 Applications Guide, AN0912A Rev. H
Other Applications
See the corresponding application in Pressure
Independent VAV Applications with CSP-5001/5002
on page 32 and make the corresponding wiring adjust-
ments for power to the MEP-4xx2 and CTE-5202.
The MEP-4xx2’s default direction is the same as the
CSP-5001.
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
24 VAC @ 5 VA
~
–
(Phase)
(Neutral)
(5K–10K
Ohm Resistor
between AI1
and Common
for Heating
Mode Only)
NC SPST
Relay
(Override
to Fully
Closed)
MEP-4002
Actuator
24 VAC
Common
Input
Out
Auto and Override (to Fully Closed)
Adding a Normally Closed SPST relay or switch
enables overriding the air ow to fully closed.
(Otherwise the example below is the same as the
conguration in Cooling or Heating on page 17).
The default seing is Auto. When the NC relay
energizes, the thermostat signal is removed from the
actuator’s input. The resulting 0 VDC “signal” on
the actuator’s input overrides the actuator to fully
closed.
NOTE: An override to fully open does not apply
to the MEP-4xx2 in a way that is analogous
to the CSP-5001 as shown in Auto and
Override (to Fully Closed or Fully Open)
on page 34.