Application Guide
Table Of Contents
- Cover/Contents
- General Information (All Applications)
- Single-Zone Proportional Heating and Cooling Applications
- Pressure Dependent VAV Applications with MEP-4xx2
- Pressure Independent VAV Applications with CSP-4702
- Replacing a CSP-5001/5002
- Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx or CSE-484x
- Cooling or Heating
- Auto and Override (to Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV Applications with CSP-5001/5002
- Cooling or Heating
- Auto and Override (to Fully Closed or Fully Open)
- Cooling with 3-Stage Reheat
- Cooling with 3-Stage Reheat and Night Setback/Setup
- Cooling with Heating Changeover
- Cooling with Heating Changeover and Electric Reheat
- Cooling with Heating Changeover and Hot Water Reheat
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Dual Duct, Minimum Air from Cold Duct
- Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series
- 9.1 VDC vs. 24 VAC Power Options
- Cooling
- Cooling with Morning Warm-Up
- Cooling with 3-Stage Reheat
- Cooling with Heating Changeover
- Cooling with Hot Water Reheat
- Fan Induction with 2-Stage Electric Heat
- Damper Tracking (Master/Slave)
- Dual Duct Heating and Cooling VAV
- Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up
- Barber Colman TP-81xx Thermostats Replacement Applications
- Index
Single-Zone Heating and Cooling Applications 12 CTE-5202 Applications Guide, AN0912A Rev. H
Heating, RA and DA
~
T
T
AI1
AO1
AO2
CTE-5202
Thermostat
24 VAC
~
–
(Phase)
(Neutral)
(5K–10K Ohm
Resistor between
AI1 and Common
for RA Mode Only)
24 VAC
Common
Input
Valve
Select Sequence 1
Select Sequence 1 Select Sequence 1
AND Set Changeover to 55° F
CTE-5202 thermostats can use a variety of valves for
heating/cooling applications with hot and chilled
water. For Reverse Acting control, connect a 5K to
10K ohm resistor between Common and AI1. Select
Sequence 1 (from the CTE-5202 SYSTEM menu)
and lower the Changeover (in the ADVANCE
menu) to the lowest seing (55° F). See Change
Conguration on page 6. The resistor simulates a
changeover sensor and puts the thermostat in Re-
verse Acting mode.
NOTE: If the resistor value is too high, the
thermostat will not go into RA mode. If
the resistor value is too low, the thermostat
may go into setback mode.
This RA control works for NO 2–10 and 0–10 VDC
valves or NC 10–2 and 10–0 VDC valves as well as
equivalent SCR controls.
For Direct Acting control, select Sequence 1 (from
the CTE-5202 SYSTEM menu). See Change Con-
guration on page 6. (Do not connect the resistor.)
This DA control works for NC 2–10 and 0–10 VDC
valves or NO 10–2 and 10–0 VDC valves as well as
equivalent SCR controls.
RA Heating
Heating
Valve Open
Setpoint
(Colder Room Temperature Warmer)
Setpoint
(Colder Room Temperature Warmer)
AO1
Signal
DA Heating
AO1
Signal
Heating
Valve Open
Heating
Valve Closed
Heating
Valve Closed
10 VDC
10 VDC