Manual
CTE-5201 2 Installation and Operation Guide
Wiring
Modular to Modular (HSO-22xx Cable)
UseHSO-22xxcablestoconnectthether-
mostattoMEP-4x42actuators,usingthe
modularconnectors,asshowninthechart
andsampleapplicationbelow.
HSO-5010 3-Way
“Y” Modular Connector
HSO-2121
Transformer Cable
CTE-5201-16 Analog Electronic Thermostat
Up to 6 MEP-4x42s
on each side
of the transformer
(with HSO-2212s)
HSO-2212
actuator cable,
12-foot length
between actuators
Wires: Orange
& Orange Stripe
T
Wires: Green
& Green Stripe
XEE-6xxx-xxx
Transformer
24 VAC (+20/–15),
4 VA Per Actuator
HSO-2250 Thermostat Cable, 50-foot (typical)
Cable P/N Cable Length
HSO-2203
3feet
HSO-2206 6feet
HSO-2212 12feet
HSO-2220 20feet
HSO-2250 50feet
Modular to Leads (HSO-5012 Cable)
IfusingtheHSO-5012cable,plugthemodularcon-
nectorintothethermostat,andconnectthestripped
leadsasfollows:
• Bluestripetoactuatorsignalinput(proportional
2–10VDC)
• Bluetopower(14–19VDC)
• GreenandGreen-Stripe(twistedtogether)to
common
•
(WiresfromPins1and6arenotconnected)
3/8"
2"